The 2026 Compliance Guide | A Practical Breakdown of Fire Hose Reels for Australian Businesses (AS 1221, AS 2441 & AS 1851)
Section 1: The 2026 Fire Hose Reel Compliance Landscape
1.1 The 2026 Critical Update: The AS 1851 Mandate
The regulatory landscape for fire safety in Australia is undergoing a critical, time-sensitive change. For businesses and building owners, the year 2026 marks a hard deadline for a new, non-negotiable compliance regime. In key jurisdictions, such as New South Wales, the previously deferred Environmental Planning and Assessment (Development Certification and Fire Safety) Amendment Regulation will take full effect.
From 13 February 2026, it becomes mandatory for all essential fire safety measures—including fire hose reels—to be maintained in strict accordance with Australian Standard AS 1851-2012: Routine service of fire protection systems and equipment.
This is a fundamental shift in legal liability. What may have been previously treated as a “best practice” guideline by some fire contractors is now a legislated requirement. Failure to adhere to the precise inspection, testing, and record-keeping protocols within AS 1851-2012 will, from this date, constitute a direct regulatory breach. This exposes building owners to significant penalties, potential invalidation of insurance, and profound legal liability in the event of a fire.
This report serves as a complete breakdown of fire hose reel (FHR) compliance, structured to prepare businesses for this 2026 deadline. It addresses the user query regarding AS 1221 but places it within the essential, larger context of the standards for installation and maintenance, which are the primary concerns for a business owner.
1.2 The “Compliance Ecosystem”: Beyond AS 1221
A business’s compliance is not governed by a single standard, but by an interconnected “ecosystem” of three. A fire hose reel system is only compliant if all three pillars are sound. Failure in one pillar renders the entire system non-compliant.
A common and costly mistake is to focus solely on the product standard, AS 1221. However, AS 1221 is a manufacturing standard; it explicitly excludes the rules for location, installation, and maintenance. A building owner’s legal responsibilities are managed across a “compliance triangle.”
This report will analyze all three standards, as summarized in the table below.
Table 1: The Fire Hose Reel Compliance Triangle
| Standard | Full Title | Primary Role (The “What”) | Primary Responsibility |
| AS/NZS 1221:1997 | Fire hose reels | The Product: Specifies how a fire hose reel must be designed, constructed, and tested by the manufacturer. | Manufacturer |
| AS 2441-2005 | Installation of fire hose reels | The Installation: Dictates where and how a compliant reel must be installed in a building to be effective (e.g., location, height, signage, and water flow). | Installer / Plumber |
| AS 1851-2012 | Routine service of fire protection systems and equipment | The Maintenance: Mandates the ongoing inspection, testing, and record-keeping required to prove the system remains functional. | Business Owner / PCBU |
1.3 The NCC Shift: Do You Even Need a Fire Hose Reel?
Before examining compliance, the first critical question a business must ask is whether a fire hose reel is required at all. For many common building types, the answer is now “no.”
The National Construction Code (NCC) sets the minimum requirements for new buildings and major refurbishments. Through successive updates (NCC 2019 and NCC 2022), the Deemed-to-Satisfy (DtS) Provisions have progressively removed the mandatory requirement for fire hose reels in many common building classes.
This policy is based on risk analysis indicating that occupants are more likely to successfully use a portable fire extinguisher for a small fire. Furthermore, the presence of a hose reel, with its “unlimited” water supply, can dangerously encourage untrained occupants to fight a fire for too long, delaying evacuation and increasing their risk of being overcome by smoke.
As detailed in Section 2, the NCC DtS provisions no longer mandate FHRs in new Class 2 (apartments), Class 3 (hotels), and Class 5 (office) buildings, among others. They are generally only required in new builds if the fire compartment is larger than 500\m2 or if an internal fire hydrant system is also installed.
1.4 The WHS Act: The Over-Arching Duty of Care
The NCC rules for new builds do not absolve businesses of their obligations for existing premises. The Work Health and Safety (WHS) Act imposes a separate, “primary duty of care” on a Person Conducting a Business or Undertaking (PCBU).
This duty is twofold:
-
Duty to Provide & Maintain: The PCBU must ensure, so far as is reasonably practicable, the provision and maintenance of a safe work environment and safe plant and equipment. If fire hose reels are present in a workplace—even if no longer mandated by the NCC for a new build—they must be maintained to the relevant standard (i.e., AS 1851) or be properly and professionally decommissioned. A neglected, non-functional reel is a significant legal liability.
-
Duty to Train: The PCBU must provide any necessary information, instruction, and training to staff to protect them from harm. If a fire hose reel is provided as workplace equipment, the PCBU must train staff in its correct and safe use, which critically includes when not to use it.
Section 2 | The Legal Framework: NCC and WHS Act Requirements (as of 2026)
2.1 The National Construction Code (NCC) 2022 & 2025
The NCC provides the technical rules for building compliance. The requirements for fire hose reels are specified in Volume One, Section E (Services and Equipment).
2.1.1 Performance Requirement E1P1
The overarching objective is stated in Performance Requirement E1P1 (formerly EP1.1). This clause requires that a fire hose reel system be installed “to the degree necessary to allow occupants to safely undertake initial attack on a fire”. This requirement is balanced against factors like the building’s size, use, fire hazard, and other safety systems (like sprinklers).
2.1.2 Deemed-to-Satisfy (DtS) Provision E1D3
For most businesses, compliance is achieved by following the prescriptive DtS provisions, specifically E1D3 (formerly E1.4 in NCC 2019). This provision outlines precisely when FHRs are required and when they are not.
When Fire Hose Reels ARE Required (E1D3(2))
A DtS solution must include fire hose reels to serve the whole building in two specific cases:
-
Where one or more internal fire hydrants are installed.
-
Where internal hydrants are not installed, but a fire compartment has a floor area greater than 500\m2.
When Fire Hose Reels ARE NOT Required (E1D3(1))
This is the most significant change for many businesses. The DtS provisions explicitly state that the requirement for fire hose reels does not apply to the following building classes 10:
- Class 2 or 3 buildings (e.g., apartment buildings, hotels, motels).
- Class 5 buildings (e.g., office buildings).
- Class 4 part of a building (e.g., a caretaker’s flat within an office).
- Class 9c buildings (aged care facilities).
- Classrooms and associated corridors in primary or secondary schools.
For these buildings, the DtS solution for first-attack firefighting is met by providing portable fire extinguishers in accordance with E1D14.
2.1.3 Future Trend (NCC 2025 Draft)
This trend of removing FHRs in favor of extinguishers is set to continue. The public comment draft for NCC 2025 includes proposals for further concessions, such as removing the requirement in small spaces that are provided with alternative, appropriate mitigation. This confirms the clear regulatory shift away from occupant-use hose reels, driven by a “workplace health and safety” approach that prioritizes early evacuation over occupant firefighting.
2.2 The Work Health and Safety (WHS) Act: Your Primary Duty of Care
The WHS Act operates in parallel with the NCC and applies to all workplaces, regardless of building age. The “Person Conducting a Business or Undertaking” (PCBU) holds a non-delegable, primary duty of care.
2.2.1 Duty to Provide and Maintain Equipment
Under the WHS Act, a PCBU must ensure, so far as is reasonably practicable, the provision and maintenance of safe systems of work and safe plant and structures. This duty explicitly extends to fire protection and firefighting equipment.
This means:
2.2.2 Duty to Provide Information, Training, and Supervision
A critical and often-overlooked component of the WHS Act is the duty to provide “any instruction, training, information, and supervision” necessary to protect all persons from risks to their health and safety.
If fire hose reels are present in the workplace, the PCBU must provide training to staff on their use. This training is not merely a “how-to” but a complete risk-management exercise. It must include:
- How to identify the different classes of fire (A, B, C, D, E, F).
- Clear and repeated instruction on which fires a hose reel can be used for (Class A only).
- Emphatic warnings on the life-threatening dangers of using a water-based reel on electrical, liquid, or fat fires.
- Procedures for evacuation and alerting authorities.
Simply installing a fire hose reel without providing this training is a breach of the PCBU’s duty of care.
Section 3: The Product Standard: A Complete Breakdown of AS/NZS 1221
This section provides a detailed, usable breakdown of AS/NZS 1221:1997, Fire hose reels. This is the manufacturing standard that defines what a compliant fire hose reel is. Understanding this standard is essential for procurement, as it ensures the product you are buying is legal and fit for purpose.
3.1 Scope and Status
-
Full Title: AS/NZS 1221:1997, Fire hose reels.
-
Current Status (for 2026): This standard was formally “Reconfirmed” in 2020. This means it has been reviewed and affirmed as the current, valid standard for manufacturing.
-
Scope (What it Covers): The standard specifies the minimum “requirements for design, construction and performance” for all new fire hose reels. It applies to both “fixed” and “swing arm” type reels designed to be used by a single operator.
-
Exclusions (What it DOES NOT Cover): The standard’s scope explicitly states that it “does not include requirements for location or maintenance of fire hose reels”. Those requirements are detailed in AS 2441 (Installation) and AS 1851 (Maintenance), respectively.
3.2 Breakdown of Section 2: Design and Construction Requirements
This section of the standard dictates the physical “build” of the reel and its components.
| Component | Clause | AS/NZS 1221 Requirement |
| Hose | 2.2.1 |
The hose must be a semi-rigid, non-kinking type. The standard size in Australia is 19mm nominal diameter and 36 metres in length. The hose is typically black or yellow and must be UV-stabilized. |
| Nozzle | 2.2.2 |
Must be a twist-type operator-controlled nozzle. It must be made of a durable, corrosion-resistant material, such as brass or an approved polymer. |
| Reel (Drum) | 2.2.3 |
The side plates of the reel must be made of a durable material (e.g., mild steel or polypropylene) and be painted or pigmented “Signal Red”. |
| Inlet Pipe & Valve | 2.2.4 & 2.2.7 |
The reel must be supplied with a DN25 (25mm) ball valve. A critical design feature is the nozzle interlock. This mechanism locks the nozzle in place, and on manual reels, it is often integrated with the valve to prevent the hose from being run out until the water valve has been turned on. |
| Fittings | 2.2.5 |
Must be supplied with all necessary components for assembly, including a wall-mounting bracket and a hose guide. |
| Cabinets | 2.3 | If a reel is supplied within a cabinet, the cabinet itself must meet design requirements, such as ensuring the door can be opened easily and does not obstruct the reel’s operation. |
3.3 Breakdown of Section 3: Performance Requirements (The Pass/Fail Tests)
This section details the mandatory tests a manufacturer must perform to certify their product. These tests prove the reel is durable and will function correctly under pressure.
-
Resistance to Internal Pressure (Clause 3.2.1 / Appendix B): The entire hose reel assembly (hose, drum, fittings) must be hydrostatically tested to withstand high pressure without leaking or failing.
-
Maximum Working Pressure: 1200 \kPa (12 bar)
-
Hydrostatic Test Pressure: 1700 \kPa (17 bar) or higher.
-
-
Strength Tests (Clause 3.2.2 / Appendices C & D): The reel must be physically robust.
-
Side Plate Test (Appendix D): The reel’s side plates are tested to ensure they resist distortion under force. They must not permanently deform by more than 5mm.
-
Load Test (Appendix C): A swing-arm reel assembly must be strong enough to support a specified load without failing.
-
-
Unwind Test (Clause 3.2.3): To prove it can be used by “one operator,” the hose must unwind freely. The test specifies that the initial pull force required to unwind the hose must not exceed 100 \Newtons
-
Discharge Tests (Clause 3.2.4 / Appendices E & F): This is the critical hydraulic performance test.
-
Flow Rate (Appendix E): This is the product capability test. The reel assembly (with its supplied hose and nozzle) must be capable of achieving a minimum discharge of 0.33 \Litres per second (19.8 \L/min) at a specified nominal inlet pressure of 220 \kPa (Note: This is different from the AS 2441 installation test, which confirms this flow rate is achieved on-site).
-
Dispersal Test (Appendix F): The nozzle must be proven to produce both an effective, coherent “JET” stream and a dispersed “SPRAY” pattern, as defined by the test parameters in the standard.
-
3.4 Breakdown of Section 4: Mandatory Marking and Identification
This section is the most practical part of AS 1221 for a business owner, as it provides the visual cues for verifying a product’s compliance. A reel that does not have these markings is not compliant.
-
On the Nozzle (Clause 4.2): The nozzle itself must be clearly and permanently marked to indicate its operation. This must include:
-
Direction of operation to the “OFF” position.
-
The “JET” position.
-
The “SPRAY” position.
-
-
On the Hose Reel (Clause 4.3): One or both side plates of the reel must be permanently marked with the following information:
-
The manufacturer’s name or trademark.
-
The Standard it complies with: AS/NZS 1221.
-
The year of manufacture.
-
The nominal hose diameter and length (e.g., “19\mm \times 36\m“).
-
The maximum working pressure (e.g., “1200 \kPa“).
-
-
Operating Instructions (Clause 4.3.3): Clear and legible operating and rewind instructions must be provided, typically on a plate or label in the center of the reel. For manual reels, this must include wording equivalent to “Turn on valve”.
-
Installation Instructions (Clause 4.6): The manufacturer must provide clear installation instructions with the product.
Actionable Table 2: AS/NZS 1221 Procurement & Audit Checklist (For Businesses)
Use this checklist when purchasing new fire hose reels or auditing existing ones to ensure the product (not its installation) is compliant.
| Verification Check | Compliance Requirement (AS/NZS 1221) | Pass / Fail |
| Reel Plate Markings |
Is the Standard “AS/NZS 1221” clearly marked on the reel side plate? |
[ ] |
|
Is the manufacturer’s name and year of manufacture visible? |
[ ] | |
|
Is the hose size (e.g., “19\mm} \times 36\m“) marked? |
[ ] | |
|
Is the maximum working pressure (e.g., “1200 \kPa“) marked? |
[ ] | |
| Are clear Operating Instructions legible on the reel? | [ ] | |
| Nozzle Markings |
Does the nozzle clearly and permanently show “JET”, “SPRAY”, and “OFF” positions? |
[ ] |
| Design |
Is the reel painted “Signal Red”? |
[ ] |
|
Is the nozzle a twist-type, made of brass or durable polymer? |
[ ] |
Section 4: The Installation Standard: A Guide to AS 2441-2005
A fully compliant AS 1221 reel is useless if it is installed incorrectly. AS 2441-2005: Installation of fire hose reels is the standard that governs where and how the reel is placed in the building.
4.1 Scope and Purpose
-
Full Title: AS 2441-2005, Installation of fire hose reels.
-
Status: This standard was reconfirmed in 2018 and remains the current, valid standard for installation as of 2026.
-
Purpose: This standard dictates the requirements for the distribution, location, and installation of FHRs to ensure adequate coverage and accessibility for “first attack” firefighting. It is the “how-to” manual for the installer.
4.2 Location and Accessibility Requirements
This is a common point of failure in building audits.
-
Proximity to Exits: Fire hose reels must be located in a readily accessible position. This is generally defined as being within 4 metres of an exit.
-
Prohibited Locations: A reel must NOT be located inside a fire-isolated exit (e.g., a fire-proof stairwell). This is a critical safety rule. If a reel were used from inside a stairwell, the fire door would be chocked open, allowing the primary escape route for all building occupants to fill with smoke.
-
Accessibility: Access to the FHR must be kept clear and unobstructed at all times.
It cannot be blocked by furniture, vending machines, stored stock, or rubbish bins.41
4.3 System Coverage: The 40-Metre Rule
AS 2441 mandates that the installation must provide 100% “system coverage” to all parts of the floor area it serves. This coverage is calculated using a specific formula:
-
The standard 36-metre hose length.
-
PLUS an assumed 4-metre water stream from the nozzle.
This creates a 40-metre coverage radius from the reel’s spindle. The installation design must ensure every part of the floor is reachable within this 40-metre arc. Furthermore, the hose must not need to be passed through a fire or smoke door to reach any part of the floor, as this would compromise the fire-rated separation.
4.4 Mounting and Physical Installation
The standard is highly specific about mounting dimensions to ensure ergonomic and safe use.
-
Spindle Height: The centre of the reel (the spindle) must be mounted between 1400mm (minimum) and 2400\mm (maximum) above the finished floor level.
-
Valve Height: The stop valve (the “tap”) must be located between 900mm (minimum) and 1100mm (maximum) above the finished floor level.
-
Clearance: A minimum radial clearance of 100\mm must be maintained from the rim of the reel to any obstruction (e.g., the side of a cabinet or an adjacent wall).
-
Protection: If a reel is installed externally or in an “aggressive environment” (e.g., subject to weather, UV, corrosive agents, or dust), it must be protected by a suitable cabinet.
4.5 Signage and Identification
AS 2441 mandates clear signage to identify the reel’s location.
-
Appearance: The location sign must feature a white pictogram (hose reel symbol) and/or text on a “Signal Red” background. The specific colour is R13 Signal Red, as defined in AS 2700.
-
Location: The sign must be installed directly above the fire hose reel.
-
Height: The base of the location sign must be no less than 2 metres from the floor. This ensures it is visible above average head height and obstructions.
4.6 Commissioning: The Critical Hydraulic Test
This is the most critical part of the installation standard and the “golden thread” of compliance. After installation, the licensed plumber must conduct a commissioning test to prove the system works as designed.
The pass/fail criteria are:
-
Flow Rate: The system must deliver a minimum discharge of 0.33 Litres per second (which is 19.8 L/min) for a standard 19mm hose.
-
Running Pressure: The system must achieve this flow rate while simultaneously maintaining a minimum running (dynamic) pressure of 220kPa at the reel’s inlet.
If the building’s mains water supply is insufficient to achieve both pressure and flow, the system is non-compliant. The only compliant solution is to install a dedicated water storage tank and a booster pump, which is a significant expense. The installer must provide a commissioning report certifying these hydraulic results. This report becomes the “baseline data” for all future maintenance under AS 1851.
Actionable Table 3: Installation Audit Checklist (Based on AS 2441-2005)
For Facility Managers to audit existing or new installations for compliance.
| Audit Point | Compliance Requirement | Site Check |
| Location |
Located within 4m of an exit. |
[ ] |
|
NOT located inside a fire-isolated stairwell. |
[ ] | |
| Accessibility |
Free from all obstructions (stock, bins, furniture). |
[ ] |
|
Path to reel is clear. |
[ ] | |
| Coverage |
Hose does NOT need to be passed through a fire/smoke door. |
[ ] |
| Mounting |
Spindle Height: 1400mm (min) to 2400mm (max) from floor. |
[ ] |
|
Valve Height: 900mm (min) to 1100mm (max) from floor. |
[ ] | |
|
Clearance: 100mm minimum from reel rim to any obstruction. |
[ ] | |
| Signage |
Red/white location sign is present and visible. |
[ ] |
|
Sign is located above the reel. |
[ ] | |
|
Base of sign is at least 2m from the floor. |
[ ] | |
| Documentation | Do you have the Commissioning Report from the installer? | [ ] |
|
Does this report confirm a flow rate of at least 0.33 L/s at 220 kPa? |
[ ] |
Section 5: The Maintenance Mandate: A Practical Guide to AS 1851-2012 (Section 9)
This section is the most critical for businesses preparing for the 2026 regulatory environment. AS 1851-2012: Routine service of fire protection systems and equipment is the “lifelong manual” that dictates your legal maintenance obligations.
5.1 The 2026 Legal Imperative
As stated in Section 1, compliance with AS 1851-2012 becomes fully mandatory in key jurisdictions like NSW from 13 February 2026. This standard is a comprehensive document covering 14 sections of fire equipment.
Adhering to this standard is not optional, and the “competent person” (i.e., your fire technician) must follow these procedures exactly.
5.2 Routine Service Frequencies (Section 9.3)
AS 1851, Section 9 sets a clear, non-negotiable service schedule for all installed fire hose reels. The frequencies are:
-
Six-Monthly (Semi-Annual): A detailed visual inspection and functional check.
-
Yearly (Annual): All six-monthly tasks plus a full hose inspection and a measured water flow test.
-
Five-Yearly: This involves a hydrostatic pressure test of the hose itself to ensure its integrity.
5.3 The Technician’s Checklist: What Your Contractor Must Do
The standard provides specific checklists (tables) for each frequency. A building owner should be aware of these tasks to properly vet their service provider.
Table 4: AS 1851-2012 (Section 9) Mandated Maintenance Schedule
| Six-Monthly Service (per Table 9.4.1) | Annual Service (per Table 9.4.2) |
|
[ ] Accessibility: Check reel is readily accessible and free from obstructions. |
[ ] All Six-Monthly Tasks: Complete every item from the 6-monthly list. |
|
[ ] Signage: Check location sign (per AS 2441) is correctly located and visible. |
[ ] Anchor Points: Check the reel is securely mounted and anchor points are tight. |
|
[ ] Operating Instructions: Check instructions on the reel plate are legible. |
[ ] Hose Inspection: Fully unwind the entire hose from the reel. Inspect its full length for cracks, frays, bulges, crazing, or other damage. |
|
[ ] Damage/Corrosion: Check all components for physical damage, leaks, or corrosion. |
[ ] Bearings/Lubrication: Check all moving parts (bearings, swing arm) and lubricate as required to ensure free operation. |
|
[ ] Nozzle: Check nozzle interlock. Check nozzle twists smoothly between all settings (OFF/JET/SPRAY). |
[ ] THE CRITICAL TEST: Full Flow Test: Conduct a measured flow test (using a flow meter and pressure gauge). |
|
[ ] Swing Arm: If fitted, check that the swing arm moves freely through its full range. |
Pass/Fail Criteria: The test must verify the system still meets its “approved design”—i.e., the 0.33 L/s at 220 kPa} “baseline data” established at commissioning. |
|
[ ] Unwind: Check that the hose unwinds freely (test pull). |
|
|
[ ] Water Flow: “Test water flow” (a brief “squirt” test) to ensure the valve is open and water is present. |
|
|
[ ] Tagging: Record all actions on the service tag. |
5.4 Common Failures vs. “Critical Defects”
During an AS 1851 inspection, the technician will classify any failures.
-
Common Defects: These are issues that must be rectified. They include leaking hoses or glands , low water pressure (below the 220 kPa minimum) , a jammed reel mechanism , significant corrosion, a damaged nozzle, or faded/missing signage.
-
“Critical Defects”: AS 1851 defines this as a defect that renders the system inoperative. This is the highest level of failure.
Examples of a “Critical Defect” include:
-
The annual flow test measures 0 L/s, meaning the stop valve is closed, the main is off, or the pipe is blocked.
-
The reel is completely obstructed by a new, bolted-down cabinet, vending machine, or stack of pallets.
-
The hose is severed, burst, or has perished to the point of being unable to hold pressure.
The consequence of a “Critical Defect” is severe. The fire technician cannot legally pass the system. This means the building owner cannot sign their Annual Fire Safety Statement (AFSS) or equivalent state-based declaration. This places the building in immediate breach of the Environmental Planning and Assessment Regulation, can void the building’s fire insurance, and may attract significant penalties from the local council or fire brigade.
5.5 Mandatory Record Keeping: Your Legal “Paper Trail”
Under the 2026 mandate, if it is not documented, it did not happen. AS 1851 (Section 1.16) and associated regulations place a heavy burden on the building owner to maintain meticulous records.
-
Service Tags: A service tag must be attached to the fire hose reel (or its cabinet). This tag, per AS 1851, must be titled “AS 1851 Service Record” and be punched or marked by the technician to show the date and type of service performed (e.g., Code 1 = six-monthly, Code 2 = yearly).
-
Logbooks: A hardcopy logbook or an approved digital summary record must be kept on-site (typically in the Fire Indicator Panel room). This logbook must record all service activities, defects found, and rectifications performed.
-
Retention Period: The building owner must keep these service reports, logbooks, and all maintenance records on-site for a minimum of 7 years. These records must be made available for inspection by an authorized person (e.g., council, fire brigade) upon request.
Section 6: Practical Risk Management: WHS-Compliant Staff Training
Fulfilling the WHS Act duty to train staff is a critical part of risk management. A fire hose reel is a powerful tool when used correctly, but a life-threatening hazard when used incorrectly.
6.1 Fire Hose Reels vs. Fire Extinguishers: Selecting the Right Tool
Staff training must begin with correct equipment selection.
-
Fire Hose Reel (FHR): Its primary advantage is a virtually unlimited supply of water connected to the mains. This makes it highly effective for controlling a large, deep-seated Class A fire. Its primary disadvantage is also the unlimited water—it encourages untrained people to stay and fight a fire that is too large, delaying evacuation.
-
Portable Fire Extinguisher: This is a limited-use, first-attack tool. Its use is finite, which inherently encourages the user to fight only very small, incipient-stage fires and evacuate if it is not quickly controlled. Different extinguishers are designed for specific fire classes (e.g., ABE, CO2, Wet Chemical).
6.2 DANGER: When NOT to Use a Fire Hose Reel
This is the most important safety message in all fire hose reel training. Water is an excellent conductor of electricity and reacts violently with certain other materials.
-
DO NOT USE ON: Class E (Electrical) Fires
-
Examples: Computers, servers, switchboards, multi-boxes, faulty wiring.
-
Danger: ELECTROCUTION. Water conducts electricity. Spraying water onto live electrical equipment will send the current back up the water stream to the user, causing severe injury or death.
-
-
DO NOT USE ON: Class B (Flammable Liquids)
-
Examples: Petrol, kerosene, solvents, oil, paint.
-
Danger: SPREADING THE FIRE. Flammable liquids float on water. Applying water will spread the burning liquid across the floor, rapidly escalating the fire.
-
-
DO NOT USE ON: Class F (Cooking Oils & Fats)
-
Examples: Deep fryers, chip pan fires.
-
Danger: VIOLENT EXPLOSION. Applying water to burning oil causes it to flash-boil, creating an explosive eruption of burning fat that will spread the fire and cause severe burns.
-
Actionable Table 5: Fire Class & First-Attack Selection Guide (For Staff Training)
| Fire Class | Fuel Source | [Icon] Fire Hose Reel | [Icon] ABE Extinguisher | [Icon] CO2 / Wet Chem |
| Class A |
Wood, Paper, Textiles
(e.g., office bin, furniture) |
YES
(Primary Tool) |
YES | OK, but ABE is better. |
| Class B |
Flammable Liquids
(e.g., petrol, solvents) |
NO – DANGER!
(Spreads Fire) |
YES | CO2 is also suitable. |
| Class E |
Electrical Equipment
(e.g., computers, switchboards) |
NO – DANGER!
(Electrocution Risk) |
YES | CO2 is preferred. |
| Class F |
Cooking Oils & Fats
(e.g., deep fryer) |
NO – DANGER!
(Explosion Risk) |
NO | Wet Chemical ONLY. |
6.3 Step-by-Step Guide: How to Safely Operate a Fire Hose Reel (For Class A Fires)
This guide should be used in all staff training and displayed near the reel.
-
ALERT: Alert everyone in the vicinity. Activate the nearest building alarm (Break Glass Alarm). Call 000 for the fire brigade.
-
ASSESS:
-
Confirm the fire is Class A (wood, paper, plastic).
-
Confirm the fire is small and not spreading rapidly.
-
Ensure you have a clear escape path behind you.
-
-
TURN ON: Go to the reel and turn the main stop valve (tap) fully ON. This will charge the hose with water and, on most models, release the nozzle interlock.
-
PULL: Grab the nozzle and pull the hose, walking towards the fire. The reel will automatically unwind. Pull out as much hose as you need, ensuring it does not get kinked.
-
AIM: Stand at a safe distance from the fire (at least 4-5 metres). Aim the nozzle at the base of the flames.
-
TWIST: Twist the nozzle slowly from “OFF” to the “JET” setting to create a solid stream of water.
-
SWEEP: Apply the water in a slow, sweeping action across the base of the fire until it appears to be completely out.
-
REWIND (After Use): Once the fire is out and the fire brigade has given clearance:
-
Turn the stop valve (tap) OFF.
-
Twist the nozzle to “JET” and aim into a drain or bucket to release the remaining pressure.
-
Rewind the hose neatly in even layers onto the reel.
-
-
REPORT: Immediately report the use to building management or your PCBU. The reel is now non-compliant until it has been inspected, tested, and re-tagged by a competent fire technician.
Section 7: Your 2026 Compliance Action Plan
The 13 February 2026 deadline for AS 1851 compliance is firm. Businesses, facility managers, and strata corporations must act now to ensure they are compliant. Use this checklist to build your action plan.
7.1 Key Actions for Building Owners & Facility Managers
-
[ ] 1. AUDIT (NCC):
-
Determine if your building legally requires fire hose reels. Check your certificate of occupancy and the NCC 2022 rules (see Section 2.1).
-
If you are a Class 2, 3, or 5 building, are your FHRs required, or were they installed under an older code?
-
Action: Engage a fire safety engineer to assess if existing FHRs can be legally (and safely) decommissioned in favor of a simpler extinguisher-based DtS solution.
-
-
[ ] 2. VET (AS 1851 CONTRACT):
-
This is the most urgent action. Locate your current fire maintenance contract.
-
Does it explicitly state that service will be provided in accordance with “AS 1851-2012”?
-
Does the quote or schedule specifically list “Section 9 – Fire Hose Reels” and detail the 6-monthly and annual tasks?
-
Action: If your contract is vague, non-compliant, or pre-dates 2012, go to tender immediately for a new, fully compliant service contract that begins before the 2026 deadline.
2
-
-
[ ] 3. REVIEW (LOGBOOKS):
-
Locate your on-site fire safety logbook and the most recent “Annual Fire Safety Statement” (AFSS) or equivalent.
-
Review the service records for the past 12-24 months.
-
Are there any “Defects” or, more seriously, “Critical Defects” listed?
-
Action: If defects are listed, find the corresponding rectification report. If there is no record of rectification, your building is non-compliant. Call your service provider immediately. Ensure all records are being kept on-site and are available for at least 7 years.
-
-
[ ] 4. TRAIN (WHS ACT):
-
Review your staff induction and ongoing training procedures.
-
Does your training include fire safety? Does it specifically cover the safe and unsafe (electrical, oil, fat fires) use of fire hose reels?.
-
Action: Implement a formal, documented training program (see Section 6) for all staff. This can be a “toolbox talk” or a session with a fire safety training provider. Document all attendance—this is your proof of compliance with the WHS Act.
-
-
[ ] 5. CHECK (AS 2441 AUDIT):
-
Perform a simple visual walk-around of your building using the checklist from Table 3.
-
Are any reels blocked by bins, stock, or furniture?.
-
Is the red and white location sign visible, in good condition, and above 2m?.
-
Is the reel itself visibly damaged or leaking?
-
Action: Rectify any simple obstructions immediately. Log any damage or signage issues for your fire contractor to fix on their next visit.
-
7.2 The Future of First-Attack Firefighting
The regulatory and safety environment has shown a clear pivot. For new buildings, the trend is to remove occupant-use hose reels from common areas, prioritizing evacuation and reliance on portable fire extinguishers and automatic sprinkler systems.
For the thousands of existing buildings, the law is moving in the opposite direction: compliance is becoming simpler for new builds but far stricter and more prescriptive for existing ones. The 2026 mandate for AS 1851-2012 is the new “line in the sand.” As of that date, ignorance of your maintenance obligations is no longer a defense, and the “it’s-on-the-wall-and-red” approach to compliance is a significant legal and financial liability.